120kw Metal Housing Heat Pump for Temperature Heating in Commercial Industrial Settings
Mode | | | WBC-120.0H-A-S(VE-BB) | ||
Hot Water Condition 1 -Ambient Temp. (DB/WB) 20/15℃,Water Temp. (In/Out):15/55℃ | Heating Capacity | kW | 87.49 | ||
| PowerInput | kW | 26.12 | ||
| Current Input | A | 44.42 | ||
| COP | WM | 3.35 | ||
Hot Water Condition 2-Ambient Temp. (DB/WB) 20/15℃,Water Temp. (In/Out):70/75℃ | Heating Capacity | kW | 87.25 | ||
| Power Input | kW | 38.78 | ||
| Current Input | A | 65.95 | ||
| COP | WM | 2.25 | ||
Heating Condition 3-AmbientTemp. (DB/WB):7/6℃, Water Temp. (In/Out):40/45℃ | Heating Capacity | kW | 78.00 | ||
| PowerInput | kW | 25.57 | ||
| CurrentInput | A | 43.49 | ||
| COP | WM | 3.05 | ||
Hot Water Condition 4-AmbientTemp. (DB/WB):7/6℃ WaterTemp. (In/Out):9/55℃ | Heating Capacly | kW | 54.00 | ||
| Power Input | kW | 27.69 | ||
| CurrentInput | A | 47.10 | ||
| COP | WM | 1.95 | ||
Power Supply | | V/Ph/Hz | 380-415V/3N-/50Hz | ||
Max Power Inpu | | kW | 67.1 | ||
Retnigarant | | type | R134a | ||
Max CurrentInpu | | A | 120.4 | ||
Highest OutletWater Temperature | | ℃ | 80 | ||
Operating Ambient Temperature | | ℃ | 5-45 | ||
Water Pressure Drop | | kPa | 70 | ||
Water Connection | | nch | DN80 | ||
Water Fow Volume | | m³/h | 20.63 | ||
Net Dimension | (L*W*H) | mm | 2600*1100*2350 | ||
PackageDimensions | (L*W*H) | mm | 2700*1150*2480 | ||
Net Weight | | kg | 1200 | ||
Gross Weight | | kg | 1250 | ||
Sound Pressure(1m) | | dB(A) | 69 |