Add to Cart
105kw Air to Water Heat Pump for Stable Operation in Shopping Malls Schools and Hospitals
Model | | | | WBC-70.0H-B-S | WBC-105.0H-A-S | WBC-180.0H-A-S | ||||
Heating Condition 1-Ambient Temp. (DB/WB): 20/15℃, Water Temp. (In/Out): 15/55℃ | Heating capacity | | kW | 66.38 | 88.50 | 177.00 | ||||
| COP | | W/W | 3.83 | 3.85 | 3.85 | ||||
| Power input | | kW | 17.33 | 22.99 | 45.97 | ||||
| Current input | | A | 31.00 | 41.12 | 82.24 | ||||
Heating Condition 2-Ambient Temp. (DB/WB): 7/6℃, Water Temp. (In/Out): 9/55℃ | Heating capacity | | kW | 54.41 | 72.54 | 145.08 | ||||
| COP | | W/W | 3.22 | 3.20 | 3.23 | ||||
| Power input | | kW | 16.90 | 22.67 | 44.92 | ||||
| Current input | | A | 30.23 | 40.55 | 80.35 | ||||
Max power input | | | kW | 26.00 | 34.48 | 68.96 | ||||
Max current input | | | A | 46.5 | 61.7 | 123.4 | ||||
Power supply | | | V~Hz | 380V 3N~ 50Hz | | | ||||
Operating ambient temperature | | | °C | -10°C~45°C | | | ||||
Water Flow Volume | | | m³/h | 11.41 | 15.22 | 30.44 | ||||
Water Pressure Drop | | | kPa | 50 | 50 | 60 | ||||
Outlet Water Temp. | | | °C | 55 | | | ||||
Max.Outlet Water Temp. | | | °C | 60 | | | ||||
Water Connection | | | inch | DN65 | DN65 | DN80 | ||||
Water pump | | | qty | 0 | 0 | 0 | ||||
Compressor | | | qty | 1 | 1 | 2 | ||||
Fan motor | | | qty | 1 | 1 | 2 | ||||
Noise | | | dB(A) | 66 | 66 | 69 | ||||
Net dimension | | L / W / H | mm | 1100*1100*1770 | 1100*1100*1770 | 1100*2290*1770 | ||||
Package dimension | | L / W / H | mm | 1120*1120*1890 | 1120*1120*1890 | 1120*2310*1890 | ||||
Net weight | | | kg | 585 | 635 | 1143 |